A8. Other typical installation examples
Electric pump control
Description
The digital outputs of the C3 can be used to control contactors associated with the
running of electric pumps (non-VSD systems). When combined with a feedback
mechanism described in subsequent sections a complete electric pump control
and monitoring system can be realised.
Electrical connection
Electric motor contactors are typically controlled by high-voltage AC
supplies, these need to be controlled by the nominal 12 VDC output of
the C3
A 12 VDC coil, 240 VAC contact relay such as the DIN rail mountable
Finder 22.21.9.012 SPST-NO relay is recommended for this purpose
Figure 37 shows control wiring using two relays to emulate the signals
provided by two existing momentary push-buttons (one for start, one for
stop)
*OUIJTDPOæHVSBUJPOUIF$PVUQVUTXJMMQVMTFPOGPSBDPOæHVSBCMFBNPVOU
of time to start and stop the pump
'PSTZTUFNTXIFSFBTJOHMFTUBUFGVMTXJUDIJTVTFEæHVSFJMMVTUSBUFT
how to use a single relay to control the pump
Note in this case it is essential that the C3 be provided with auxiliary power
(usually from the available mains supply) to ensure the battery does not
become depleted from the draw associated with keeping the relay active
while the pump is running
Installation notes
It is typical for the C3 and associated wiring to be housed within the same
switch-box as the electric pump contactor
Both the C3 and relay(s) can be mounted on standard 25 mm DIN rail
If mains power is available it is recommended to install a 12 VDC power
supply connected to the auxiliary power input of the C3